Energy Savings Improves Efficiency and Profit

044 - 2476 8113

UNIVERSAL POWERTECH ENGINEERING

LV Capacitor QCap

LV Capacitor QCap

The ABB cylindrical capacitor

Power Quality is a major concern to all size of business, be it industrial or commercial. It impacts energy usage costs, pollution levels and CO2 emissions, equipment failure, malfunctioning and lifetime reduction but also maintenance costs.

The ABB QCap will help to improve the Power Quality of low voltage installations by addressing poor power factor issues.

abb

The QCap is the cylindrical power factor correction capacitor based on ABB‘s latest technologies and developments. This is the result of more than a century of know how on electrical engineering and 70 years expertise on capacitor technologies.

ABB QCap capacitor answers customer needs

Reliability: customers can easily become victims of poor quality capacitors made with non-capacitor gradefilm. ABB strict selection of raw material and its first class capacitor film ensure QCap a high reliability

Quality: ABB low losses design decreases capacitor tempera- ture and increases the lifetime. The optimized thermal dissipation will prevent the premature failure which is not uncommon with many low quality capacitors.

Safety: at the end of its lifetime the capacitor must disconnect itself safely. The ABB designed over pressure disconnection device guarantees a safe disconnection.

Consistency: a constant quality over the time is most often a challenge for manufacturers. It‘s the reason why ABB is testing 100% of the products with criteria surpassing international standards.

Safety

Safety is definitely one of the most important topic for a capacitor. The customer has to be sure that in case of issues the damage will be limited.

Over pressure disconnection

ABB safety concept and mechanism guarantee a prompt and reliable breaking of all three wires under faulty conditions. This concept consists of three parts:

Airtight: the state-of-the-art beaming and seaming technology and equipment ensure a perfectly hermetic cylinder.

Lock: the ABB unique design on a locking device to contain the three elements tight under both normal and faulty conditions.

Snap: with the airtight and the lock as prerequisites, the snap will break three wires promptly and completely.

Range

50 Hz

Network voltage Rated power [kvar] Article number for ordering
400V 12.5 2GCA294450A0031
15 2GCA294451A0031
20 2GCA294452A0031
25 2GCA294453A0031
415V 12.5 2GCA294454A0031
15 2GCA294455A0031
21.6 2GCA294452A0031
25 2GCA294456A0031
440V 12.9 2GCA294457A0031
14.2 2GCA294463A0031
15 2GCA294458A0031
20 2GCA294459A0031
25 2GCA294460A0031
28.2 2GCA294461A0031
480V 12.5 2GCA294462A0031
15.4 2GCA294457A0031
16.7 2GCA294463A0031
20.9 2GCA294473A0031
25 2GCA294464A0031
525V 12.5 2GCA294465A0031
15 2GCA294466A0031
20 2GCA294467A0031
25 2GCA294468A0031

60 Hz

Network voltage Rated power [kvar] Article number for ordering
380V 12.5 2GCA294454A0031
15 2GCA294455A0031
21.7 2GCA294452A0031
25 2GCA294456A0031
400V 12.5 2GCA294469A0031
15 2GCA294450A0031
20 2GCA294470A0031
24.1 2GCA294453A0031
440V 12.5 2GCA294462A0031
15 2GCA294457A0031
20 2GCA294471A0031
25 2GCA294464A0031
30 2GCA294460A0031
480V 12.5 2GCA294472A0031
15 2GCA294462A0031
18 2GCA294457A0031
20 2GCA294463A0031
25 2GCA294473A0031
30 2GCA294464A0031
525V 12 2GCA294474A0031
15 2GCA294465A0031
18 2GCA294466A0031
20 2GCA294475A0031
24 2GCA294467A0031
30 2GCA294468A0031
600V 12 2GCA294477A0031
15 2GCA294478A0031
18 2GCA294479A0031
20 2GCA294480A0031
25 2GCA294481A0031
30 2GCA294482A0031

Technical Specifications

Voltage range From 380 to 600 V.
Frequency 50 and 60 Hz.
Connection Three-phase.
Net output  power From 12.5 to 30 kvar.
Tolerance on capacitance 0% / +10%.
Losses < 0.2 Watt/kvar (dielectric only).
< 0.5 Watt/kvar (including discharge resistor).
Discharge resistor  Discharge from Un to 50V in 1 minute.
Maximum permissible  current 1.3 x In for continuous operation.
Tolerance on voltage 30% for maximum 1 minute.
Case material Recyclable aluminum.
Color Raw aluminum.
Fixing 1 stud (M12).
Dimensions (DxH) 90x417mm.
Weight Approximately 3kg.
Terminals Cage screws.
Minimum distance above unit 20mm.
Earth Earth connection on the enclosure fixation.
Execution Indoor use only.
Temperature range -25°C / +55°C (class D according to IEC 60831).
Altitude Up to 2000m.
Protection  degree IP20.

Dimensions

Total H (mm) Can H (mm) D (mm) D fixation screw(mm) H fixation screw
401 368 90 M12 16

Rated voltage - 415V Three Phase 7 % Detuned reactor

Design: Three-phase, iron-core with air gaps

Technical Data:

No. of phases 3 3 3 3 3 3 3 3
Rated voltage Un/V 415 415 415 415 415 415 415 415
Rated frequency fn/Hz 50 50 50 50 50 50 50 50
Reactance factor P/% 7 7 7 7 7 7 7 7
Resonanc e frequency Fr/Hz 188.9

8

188.9

8

188.9

8

188.9

8

188.

98

188.9

8

188.98 188.98
Reactive power Nc/kVAr 5 7.5 10 12.5 15 25 50 100
Rated inductivit y Ln/mH 3X8.2

6

3X5.5

0

3X4.1

3

3X3.3

0

3X2.

75

3X1.6

52

3X0.82

6

3X0.41

3

Tolerance % +/-3 +/-3 +/-3 +/-3 +/-3 +/-3 +/-3 +/-3
RMS

current

Irms/A 7.65 11.47 15.30 19.13 22.9

5

38.26 76.51 153.03
Linearity % 160 160 160 160 160 160 160 160
Total losses Nvsum/ W 25 54 54 79 79 97 168 278

Operating Conditions:

Protection class IP00, Indoor operation
Type of cooling AN natural convection
Isolation class T50/F
Minimum ambient temperature Tamin/°C 5 (no condensing, no ice)
Maximum ambient temperature Tamax/°C 50
Allowed temperature rise dT/K 95
Temperature sensor No

Standards:

  • IEC standards
  • IEC/EN60076-6